Deluxia Palace, Barbaros Mah. Mor Sümbül Sok. No:5A/88 Kat:3, Ataşehir / İstanbul [email protected]

FFS07 and FFS08 flame sensors

UV/IR flame sensors that work only with F152, CMS, ETAMATIC, ETAMATIC OEM or MCC-BC400; FFS07 also comes in Ex versions

Flame monitoring

LAMTEC · FFS07 · FFS08

  • UV · IR
  • SIL3 (F152) · Continuous
  • FFS07: Ex 1/21 · Ex 2/22

The FFS07 and FFS08 flame sensors are of the non-compact type: FFS07 points axially at the flame, while FFS08 sits at right angles to the flame axis. Together with the F152 flame monitoring device they supervise burner flames safely in applications that do not call for demanding flame discrimination. They work only with F152, CMS, ETAMATIC, ETAMATIC OEM or MCC-BC400 and take their 24–42 V DC supply through these devices; each F152 accepts a single sensor. They are meant for single-burner systems and serve heating plants with single- or multi-fuel burners, process firing systems and hydrogen plants.

The sensors measure in the UV or IR range, chosen according to the fuel. UV-1 (260–400 nm) suits oil and gas; UV-4 (215–360 nm) also suits special gases such as refinery and furnace gas; IR-1 (1000–2500 nm) suits oil and gas firing with strong flue gas recirculation, and yellowish waste gases without UV or with the UV screened. The UV sensor detects within an 8° viewing angle, the IR sensor within 60°. Both models also offer the IR-1 T type, and FFS08 additionally IR-1 T/S2. They can be used outdoors; with F152 they run continuously and meet SIL3 to DIN EN 61508-2.

FFS07 is offered for safe areas, as FFS07 Ex-II for Ex zones 2 and 22 and as FFS07 Ex for Ex zones 1 and 21; FFS07 Ex is marked Ex d IIC T6 Gb and Ex tb IIIC T80 °C Db. Protection is IP66 in Ex zone 1 and IP67 in Ex zone 2. FFS07 fits plug-in FH or threaded FV brackets, and only FV brackets in Ex zone 1. FFS08 is for safe areas only: it has a nickel-plated brass housing and IP67, comes in short and long versions, and fits FH80 or FS60 brackets. Cable lengths stay below 300 m for both sensors.

FFS07 and FFS08 flame sensors
FFS07 and FFS08 flame sensors 1FFS07 and FFS08 flame sensors 2FFS07 and FFS08 flame sensors 3FFS07 and FFS08 flame sensors 4FFS07 and FFS08 flame sensors 5FFS07 and FFS08 flame sensors 6FFS07 and FFS08 flame sensors 7
Benefits

FFS07 and FFS08 flame sensors

  • Sensors for UV and IR: types UV-1, UV-4 and IR-1
  • Continuous operation and SIL3 to DIN EN 61508-2 together with F152
  • For use with the F152 flame monitoring device as well as CMS, ETAMATIC, ETAMATIC OEM and MCC-BC400
  • FFS07 points axially at the flame, FFS08 sits at right angles to the flame axis
  • FFS07 versions for Ex zones 1 and 21 (FFS07 Ex) and Ex zones 2 and 22 (FFS07 Ex-II)
  • Suitable for outdoor use; cable lengths below 300 m
  • EU type examination certificates (2014/68/EU, (EU) 2016/426), UL 60730-2-5 and IACS UR E10 ship certification
FFS07 · FFS08

Key specifications

SpecificationFFS07FFS08
Flame detectionUV-1 260 … 400 nm · UV-4 215 … 360 nm · IR-1 1000 … 2500 nm · IR-1 TUV-1 260 … 400 nm · UV-4 215 … 360 nm · IR-1 1000 … 2500 nm · IR-1 T · IR-1 T/S2
Viewing angleUV: 8° · IR: 60°UV: 8° · IR: 60°
Operating modeContinuousContinuous
Supply voltage24 … 42 V DC (via the evaluation unit)24 … 42 V DC (via the evaluation unit)
Used withF152 · CMS · ETAMATIC · ETAMATIC OEM · MCC-BC400F152 · CMS · ETAMATIC · ETAMATIC OEM · MCC-BC400
Explosion protection (Ex)Ex zones 1 and 21 (FFS07 Ex) · Ex zones 2 and 22 (FFS07 Ex-II)Not for Ex zones
Degree of protectionIP66 (Ex zone 1) · IP67 (Ex zone 2)IP67
Ambient temperature-20 … +65 °C (UV) · -20 … +60 °C (IR)-20 … +65 °C (UV) · -20 … +60 °C (IR)
Cable length< 300 m< 300 m
Safety integrity levelSIL3 (F152)SIL3 (F152)

Full technical data: data sheet(opens in a new tab)

Approvals and standards

  • CE declaration of conformity (2014/35/EU, 2014/30/EU, 2014/68/EU, (EU) 2016/426, 2011/65/EU, 2015/863/EU)
  • EU type examination certificate — 2014/68/EU, Module B (pressure equipment)
  • EU type examination certificate — (EU) 2016/426 (gas appliances)
  • SIL3 — DIN EN 61508
  • DIN EN 298
  • DIN EN 13611
  • DIN EN 60730-2-5
  • DIN EN 60730-1
  • UL 60730-2-5 (US)
  • Ship certification — IACS UR E10 Rev. 8
  • Ex zone 1 — IEC 60079-0, -1, -7, -11, -28, -31 (FFS07 Ex)
  • Ex zone 2 — IEC 60079-0, -7, -31 (FFS07 Ex-II)

Accessories

  • FS60-00 bracket for FFS08: without adjusting ring, anodised aluminium
  • FS60-10 bracket for FFS08: with adjusting ring, anodised aluminium
  • FS65 cooling air housing for FFS08: with bracket, air connection pivotable by ±90°
  • FH80-00 adjustment bracket for FFS08: G 1/2" purge air connection, insulating part
  • FH80-10 adjustment bracket for FFS08: with globe joint and G 1/2" purge air connection
  • FFP30 flame scanner testing device: flame simulation for UV and IR sensors in four changing frequency ranges; plugs onto FFS07 and FFS08
  • FR20-01 bracket with 90° deflecting mirror for FFS07: plug-in and threaded variants, nickel-plated brass, quartz glass

Documents

Let's choose the right product for your project together

Tell us about your plant and what you need, and our engineers will recommend the right solution.