F152 flame monitoring device
SIL3 evaluation unit for optical flame monitoring with an FFS07 or FFS08 UV/IR sensor, approved for continuous operation
LAMTEC · F152
- SIL3
- UV · IR (FFS07 / FFS08)
- Continuous
- 10 … 200 Hz
Paired with an FFS07 or FFS08 flame sensor, F152 forms a safety arrangement that optically watches the flames of single-burner systems, for applications that do not call for demanding flame discrimination. It works only with these two sensors, and each F152 takes a single sensor. The sensors measure in the UV or IR range, which is chosen to suit the fuel. F152 is approved for continuous operation and certified to SIL3 under DIN EN 61508-2.
The unit has a plastic housing with integrated control electronics and mounts on a DIN rail. Thanks to its two-channel design with electronic self-monitoring, no mechanical shutter is needed. It evaluates the flame frequency digitally between 10 and 200 Hz, shows its states on LEDs and has a 0…20 mA intensity output as standard. No adaptation to national mains frequencies is required. The status contact (NC) and the flame signal contact (NO) are floating changeover contacts.
F152 serves single- or multi-fuel burners in heating plants, power plants, process furnaces and standard boiler applications, firing oil, gas, biomass, dust or process gases. The standard supply voltage is 230 V AC; a 115 V AC version is prepared at the factory on request. It fulfils DIN EN 298 and, for process burners, DIN EN 746-2.
F152 flame monitoring device
- Optical flame monitoring in the UV or IR range with an FFS07 or FFS08 sensor
- Approved for continuous operation; SIL3 to DIN EN 61508-2
- Digital evaluation of the flame frequency between 10 and 200 Hz
- Two-channel design with electronic self-monitoring, so no mechanical shutter is needed
- 0…20 mA intensity output as standard and LED status indication
- DIN-rail module that needs no adaptation to national mains frequencies
- EU type examination certificates to (EU) 2016/426 and 2014/68/EU, UL 60730-2-5 and IACS UR E10 ship certification
Key specifications
| Specification | F152 |
|---|---|
| Flame detection | UV · IR (FFS07 / FFS08) |
| Operating mode | Continuous |
| Flame frequency evaluation | 10 … 200 Hz |
| Analogue outputs | 0 … 20 mA (flame intensity) |
| Supply voltage | 230 V AC +10/-15 % · 115 V AC +10/-15 % |
| Power consumption | ≤ 5 VA |
| Degree of protection | IP20 |
| Ambient temperature | -10 … +60 °C |
| Safety integrity level | SIL3 |
Approvals and standards
- CE declaration of conformity (2014/35/EU, 2014/30/EU, 2014/68/EU, (EU) 2016/426, 2011/65/EU, 2015/863/EU)
- EU type examination certificate — 2014/68/EU, Module B (pressure equipment)
- EU type examination certificate — (EU) 2016/426 (gas appliances)
- SIL3 — DIN EN 61508
- DIN EN 298
- DIN EN 13611
- DIN EN 60730-2-5
- DIN EN 60730-1
- UL 60730-2-5 (US)
- Ship certification — IACS UR E10 Rev. 8
- UKCA marking (United Kingdom)
More products in this group
F120I flame monitoring device
SIL3 DIN-rail device that supervises gas flames by ionisation, using a 390 V auxiliary voltage
- SIL3
- Ionisation · 390 V
- Intermittent · Continuous
F130I flame monitoring device
SIL3 flame monitor with ionisation, UV tube and LDR inputs, approved for continuous operation with ionisation
- SIL3
- Ionisation · UV · LDR
- Continuous (ionisation only)
F200K compact flame scanner
SIL3 compact flame scanner with a UV or IR sensor and evaluation electronics in one housing, for continuous operation
- SIL3 · IP67
- UV-2 · IR-1 · IR-2
- 24 V DC
F200K Ex explosion-protected compact flame scanner
SIL3 compact flame scanner for hazardous areas: F200K Ex for Ex zones 1 and 21, F200K Ex-II for zones 2 and 22
- Ex 1/21 · Ex 2/22
- SIL3 · Continuous
- UV-2 · IR-1
Let's choose the right product for your project together
Tell us about your plant and what you need, and our engineers will recommend the right solution.