F120I flame monitoring device
SIL3 DIN-rail device that supervises gas flames by ionisation, using a 390 V auxiliary voltage
LAMTEC · F120I
- SIL3
- Ionisation · 390 V
- Intermittent · Continuous
- -20 … +70 °C
F120I is a safety device that supervises pilot and main flames of gaseous fuels by ionisation; LAMTEC developed it from its F130I. In both intermittent and continuous operation it applies a 390 V ionisation auxiliary voltage. This measuring method lets each flame be watched on its own in single- and multi-burner systems. It is aimed at power stations, the chemical industry and industrial firing plants that need a flame monitor meeting SIL3.
The control electronics are built into the housing, and the device is mounted on a DIN rail in the control cabinet. Its two-channel design checks itself electronically, LEDs show the status, and it needs no adaptation to national mains frequencies. Both single- and two-electrode operation are supported. For the flame failure detection time (FFDT), values of 1 s, 3 s and 5 s are given, and the permitted ambient temperature is -20…+70 °C.
Outputs: digital signals for status and flame, a relay contact for the flame signal, open-collector outputs for flame ON and standby, and analogue outputs for ionisation voltage and flame intensity (4…20 mA). F120I is not meant to close fuel valves directly: the signal from its safe output contact has to be processed further in the plant's higher-level control system. It is supplied from the factory for 230 V AC or 115 V AC.
F120I flame monitoring device
- Ionisation supervision of pilot and main flames on gaseous fuels, in intermittent and continuous operation
- 390 V ionisation auxiliary voltage; single- and two-electrode operation
- Each flame watched on its own in single- and multi-burner systems
- SIL3 to DIN EN 61508; EU type examination certificates to 2014/68/EU and (EU) 2016/426
- Two-channel design with electronic self-monitoring, as a module for DIN-rail mounting
- 4…20 mA flame intensity output, open-collector outputs and an LED intensity display
- Fulfils DIN EN 298 and, for process plants, DIN EN 746-2
- Works on any national mains frequency without adjustment
Key specifications
| Specification | F120I |
|---|---|
| Flame detection | Ionisation |
| Operating mode | Intermittent · Continuous |
| Ionisation auxiliary voltage | 390 V |
| Flame failure detection time (FFDT) | 1 s · 3 s · 5 s |
| Supply voltage | 230 V AC · 115 V AC |
| Analogue outputs | 4 … 20 mA (flame intensity) · ionisation voltage |
| Ambient temperature | -20 … +70 °C |
| Safety integrity level | SIL3 |
Approvals and standards
- CE declaration of conformity (2014/35/EU, 2014/30/EU, 2014/68/EU, (EU) 2016/426, 2011/65/EU, 2015/863/EU)
- EU type examination certificate — 2014/68/EU, Module B (pressure equipment)
- EU type examination certificate — (EU) 2016/426 (gas appliances)
- SIL3 — DIN EN 61508
- DIN EN 298
- DIN EN 13611
- DIN EN 50156-1
- DIN EN 50156-2
- DIN EN 60730-2-5
- DIN EN 60730-1
More products in this group
F130I flame monitoring device
SIL3 flame monitor with ionisation, UV tube and LDR inputs, approved for continuous operation with ionisation
- SIL3
- Ionisation · UV · LDR
- Continuous (ionisation only)
F152 flame monitoring device
SIL3 evaluation unit for optical flame monitoring with an FFS07 or FFS08 UV/IR sensor, approved for continuous operation
- SIL3
- UV · IR (FFS07 / FFS08)
- Continuous
F200K compact flame scanner
SIL3 compact flame scanner with a UV or IR sensor and evaluation electronics in one housing, for continuous operation
- SIL3 · IP67
- UV-2 · IR-1 · IR-2
- 24 V DC
F200K Ex explosion-protected compact flame scanner
SIL3 compact flame scanner for hazardous areas: F200K Ex for Ex zones 1 and 21, F200K Ex-II for zones 2 and 22
- Ex 1/21 · Ex 2/22
- SIL3 · Continuous
- UV-2 · IR-1
Let's choose the right product for your project together
Tell us about your plant and what you need, and our engineers will recommend the right solution.