Deluxia Palace, Barbaros Mah. Mor Sümbül Sok. No:5A/88 Kat:3, Ataşehir / İstanbul [email protected]

F200K Ex explosion-protected compact flame scanner

SIL3 compact flame scanner for hazardous areas: F200K Ex for Ex zones 1 and 21, F200K Ex-II for zones 2 and 22

Flame monitoring

LAMTEC · F200K Ex · F200K Ex-II

  • Ex 1/21 · Ex 2/22
  • SIL3 · Continuous
  • UV-2 · IR-1

F200K Ex and F200K Ex-II are the Ex versions of the F200K compact flame scanner, designed for potentially explosive atmospheres. The flame sensor and the switching amplifier share one housing, so no separate evaluation unit is needed. The scanner supervises the flame in continuous operation on firing systems with one or more burners and is certified to SIL3 under DIN EN 61508-2. The Ex design opens F200K up to further uses, above all in the chemical and petrochemical industry. F200K Ex is marked for Ex zones 1 and 21, F200K Ex-II for Ex zones 2 and 22.

Both models are available with a UV-2 (210–380 nm) or an IR-1 (1200–2800 nm) sensor. UV-2 is preferred for oil, gas and special gases like refinery gas, blast furnace gas and hydrogen; IR-1 for oil, gas, wood and coal firing with heavy flue gas recirculation, and for yellowish waste gases that emit no UV or whose UV part is screened by water vapour and dust. Sensitivity is set in several stages and the flame frequency is evaluated digitally; the two-channel design monitors itself electronically. The supply is 24 V DC ± 20 %, power consumption is up to 4 W and the analogue output is 0/4…20 mA.

F200K Ex has a nickel-plated, varnished aluminium housing rated IP66; it operates at ambient temperatures of -40…+65 °C with the UV-2 sensor and -40…+60 °C with IR-1, and it mounts only on threaded FV30 or FV40 brackets. F200K Ex-II is rated IP66/67, operates at -40…+75 °C with UV-2 and -40…+60 °C with IR-1, and mounts on threaded FV30/FV40 or plug-in FH30/FH40 brackets. The FS50 cooling air housing can be used with F200K Ex-II, while no cooling air housing is offered for Ex zone 1. On F200K Ex-II, the 3 m connecting cable can be extended by up to 250 m at a 20.5 V supply. A UV-6 FO fibre-optic sensor variant is also available for F200K Ex-II in Ex zone 2.

F200K Ex explosion-protected compact flame scanner
F200K Ex explosion-protected compact flame scanner 1F200K Ex explosion-protected compact flame scanner 2F200K Ex explosion-protected compact flame scanner 3
Benefits

F200K Ex explosion-protected compact flame scanner

  • F200K Ex for Ex zones 1 and 21, F200K Ex-II for Ex zones 2 and 22
  • Flame sensor and switching amplifier in one compact housing; no separate evaluation unit
  • Continuous operation on single- and multi-burner systems; SIL3 to DIN EN 61508-2
  • Ex design especially suited to chemical and petrochemical applications; UV-2 or IR-1 sensor
  • Multi-stage sensitivity setting and digital flame frequency evaluation
  • LED status display and a connectable trend display for aligning the scanner on the flame
  • Two-channel system with electronic self-monitoring
  • EU type examination certificates (2014/68/EU, (EU) 2016/426), IEC 60079 Ex zone 1 certificate for F200K Ex, Ex zone 2 for F200K Ex-II, UL 372 and CSA C22.2 No. 199
F200K Ex · F200K Ex-II

Key specifications

SpecificationF200K ExF200K Ex-II
Flame detectionUV-2 210 … 380 nm · IR-1 1200 … 2800 nmUV-2 210 … 380 nm · IR-1 1200 … 2800 nm
Operating modeContinuousContinuous
Supply voltage24 V DC ± 20 %24 V DC ± 20 %
Power consumption≤ 4 W≤ 4 W
Analogue outputs0/4 … 20 mA, load 200 Ω0/4 … 20 mA, load 200 Ω
Explosion protection (Ex)Ex zones 1 and 21 · II 2G Ex db IIC T6…T5 Gb · II 2D Ex tb IIIC T80 °C, T95 °C DbEx zones 2 and 22 · II 3G Ex nA nC IIC T6…T5 Gc X · II 3D Ex tc IIIC T85 °C Dc X
Degree of protectionIP66IP66/67
Ambient temperature-40 … +65 °C (UV-2) · -40 … +60 °C (IR-1)-40 … +75 °C (UV-2) · -40 … +60 °C (IR-1)
Safety integrity levelSIL3SIL3

Full technical data: data sheet(opens in a new tab)

Approvals and standards

  • CE declaration of conformity (2014/35/EU, 2014/30/EU, 2014/68/EU, (EU) 2016/426, 2011/65/EU, 2015/863/EU)
  • EU type examination certificate — 2014/68/EU, Module B (pressure equipment)
  • EU type examination certificate — (EU) 2016/426 (gas appliances)
  • SIL3 — DIN EN 61508
  • DIN EN 298
  • DIN EN 13611
  • DIN EN 50156-1
  • DIN EN 60730-2-5
  • DIN EN 60730-1
  • UL 372 (US)
  • CSA C22.2 No. 199 (CA)
  • Ex zone 1 — IEC 60079-0, -1, -7, -11, -28, -31 (F200K Ex)
  • Ex zone 2 — IEC 60079-0, -7, -15, -31 (F200K Ex-II)
  • ANSI/ISA-12.12.01-2015 — Class I, Division 2 hazardous locations (US)
  • CSA C22.2 No. 213-15 — Class I, Division 2 hazardous locations (CA)

Accessories

  • Threaded FV30 and FV40 brackets, including types with purge air connection and globe joint
  • FG24 Ex-II junction box (F200K Ex-II, Ex zone 2): marked II 3G, IP66, four screwed cable glands
  • FFP30 testing device: simulates a varying flame frequency and screws onto the scanner, which must be set sensitive enough to detect the simulation

Documents

Let's choose the right product for your project together

Tell us about your plant and what you need, and our engineers will recommend the right solution.