Deluxia Palace, Barbaros Mah. Mor Sümbül Sok. No:5A/88 Kat:3, Ataşehir / İstanbul [email protected]

XE 18 PBA 04 portable high-energy igniter, Ex d

Battery-powered portable high-energy igniter in a flameproof enclosure for Ex zones 1 and 2

Ignition systems

TESI · XE 18 PBA 04

  • 18 J · ≈ 4 Hz
  • Ex d IIC T5 · Ex 1/2
  • Battery 12 V · 3.6 Ah
  • IP66

The TESI XE 18 PBA 04 is a portable high-energy igniter for lighting burners that have no pilot burner or electrode set of their own; it also serves as a standby when an installed igniter fails or in an emergency. Its aluminium-alloy enclosure is certified ATEX II 2G Ex d IIC T5 IP66, so it may be used in Ex zones 1 and 2.

It needs no mains connection: a built-in 12 V, 3.6 Ah Ni-Cd battery and an automatic charger power it. Each spark carries 18 J at roughly four sparks per second, and one charge lasts for up to 12,400 sparks at the standard duty cycle. Because the input voltage is low, operators can hold the rod during maintenance without risk of an electric shock.

The stainless-steel ignition rod works at 760 °C (1000 °C at most), is made to the required length and has an easily replaced 17 mm high-energy tip (12 or 14 mm on request). A flexible stainless armoured cable with 1/2 NPT fittings connects it. Mains charging is allowed only in non-classified areas, with the gas-evacuation cap fully open.

XE 18 PBA 04 portable high-energy igniter, Ex d
XE 18 PBA 04 portable high-energy igniter, Ex d 1XE 18 PBA 04 portable high-energy igniter, Ex d 2XE 18 PBA 04 portable high-energy igniter, Ex d 3
Benefits

XE 18 PBA 04 portable high-energy igniter, Ex d

  • ATEX II 2G Ex d IIC T5 IP66 enclosure for use in Ex zones 1 and 2
  • No mains connection needed: built-in 12 V Ni-Cd battery and charger
  • 18 J per spark at about four sparks per second
  • Up to 12,400 sparks per charge (60 °C, standard duty cycle)
  • Lights every type of fuel, including in demanding applications
  • Safe handling during maintenance thanks to the low input voltage
Functions

XE 18 PBA 04 portable high-energy igniter, Ex d

Use

  • Lighting burners that have no igniter of their own
  • Standby ignition when an installed igniter fails
  • Ignition in emergencies
XE 18 PBA 04

Key specifications

SpecificationXE 18 PBA 04
Ignition energy18 J
Spark rate≈ 4 Hz
Supply voltage12 V DC (internal rechargeable battery, Ni-Cd, 3.6 Ah)
Battery runtime≤ 12 400 sparks (60 °C, standard duty cycle)
Duty cycle100 % (suggested max. continuous sparking time: 30 min)
Explosion protection (Ex)II 2G Ex d IIC T5 (Ex zones 1 and 2)
Degree of protectionIP66
Ambient temperature-20 … +60 °C (special execution: -30 … +60 °C)
Dimensions355 × 270 × 165 mm (special execution: 355 × 325 × 174 mm)
Weight10 kg (special execution: 15 kg)

Full technical data: data sheet(opens in a new tab)

Approvals and standards

  • ATEX II 2G Ex d IIC T5 IP66 (Ex zones 1 and 2)