GFI pilot burner
Gas-fired pilot burner with flame monitoring for reliable main burner ignition in industrial furnaces and firing systems
LAMTEC · GFI35 · GFI48 · GFI70 …
- 27 … 700 kW
- SIL3 · IP65
- ATEX · IECEx (GFI48, GFI70, GFI89)
- Intermittent · Continuous
GFI series pilot burners light the main burner safely in industrial furnaces, thermal process plants and boilers fired with gas, oil or solid fuels. They serve to preheat the plant, to light the main burner and to support its flame. The GFI itself runs on natural gas or LPG, with coke oven gas and special gases as options, and it can light main burners burning any kind of gas, light fuel oil or heavy fuel oil.
In the standard version, the ignition transformer, the ionisation electrode and a SIL3-certified, EU type-examined ionisation flame monitor are built into the burner. It works on the forced-air, nozzle-mixing principle: no external gas-air mixer is needed, the supply lines carry no ignitable mixture and the flame does not flash back. The flame forms locally and is monitored at one spot. Flame monitoring is approved for continuous operation, and the response time when the flame goes out is selectable as up to 1 s or up to 3 s. The ignition voltage is up to 8 kV with a 230 V supply and up to 7 kV with a 120 V supply; in Ex zone 2, up to 5 kV applies to both.
The series comprises four sizes, GFI35, GFI48, GFI70 and GFI89, with tube diameters of 35, 48.3, 70 and 88.9 mm. Electrical data are the same for all sizes, which differ only in gas and air flow. GFI35 is intended for the safe area; GFI48, GFI70 and GFI89 are available for the safe area and Ex zone 2 and, with an external power unit, also for Ex zone 1. Versions with or without a film display exist, and the tube length is set between 300 and 6000 mm when ordering.
GFI pilot burner
- Nozzle-mixing principle: no external gas-air mixer and no ignitable mixture in the supply lines
- No flashback; local flame formation and spot flame monitoring
- Integrated ignition transformer and SIL3 ionisation flame monitoring in the standard version
- Intermittent or continuous operation
- Four standard sizes covering thermal outputs from 27 kW to 700 kW
- IP65 protection; Ex zone 1 and Ex zone 2 versions for GFI48, GFI70 and GFI89
GFI pilot burner
External power unit
Two types are available. Safe-area type: steel housing painted RAL 7035, IP66, -20…+60 °C. Ex zone 1 type: copper-free aluminium and 1.4404/316 stainless steel, marked II 2G Ex db IIB+H2 T6/T5 Gb and II 2D Ex tb IIIC T80…T95 °C Db, certificates ITS 15 ATEX 18302X and IECEx ITS 15.0041X, IP66, 7 J impact resistance, -20…+60 °C. With this unit the pilot burner is rated for -20…+80 °C with the standard threaded connection and -40…+80 °C with an Ex I conduit threaded connection.
Key specifications
| Specification | GFI35 | GFI48 | GFI70 | GFI89 |
|---|---|---|---|---|
| Thermal output | 27 … 57 kW | 70 … 140 kW (natural gas) · 70 … 130 kW (propane) | 150 … 300 kW | 400 … 700 kW |
| Flame length | ≤ 600 mm | ≤ 800 mm | ≤ 1200 mm | ≤ 2000 mm |
| Gas flow (at 200 mbar inlet pressure) | 5.8 Nm³/h (natural gas, propane) | 15 Nm³/h (natural gas) · 6 Nm³/h (propane) | 30 Nm³/h (natural gas) · 12 Nm³/h (propane) | 70 Nm³/h (natural gas) · 28 Nm³/h (propane) |
| Flange connection | DN 50 / PN 6 | DN 50 / PN 6 | DN 65 / PN 6 | DN 80 / PN 6 |
| Specification | GFI |
|---|---|
| Fuels | Natural gas, LPG · coke oven gas and special gases (optional) |
| Supply voltage | 220–230 / 120–127 V AC +10/-15 %, 50/60 Hz |
| Flame detection | Ionisation (F130I) |
| Safety integrity level | SIL3 |
| Degree of protection | IP65 · NEMA 4 / 4X |
| Ambient temperature | -20 … +60 °C (without display) · 0 … +60 °C (with display) |
Approvals and standards
- CE declaration of conformity (2014/35/EU, 2014/30/EU, (EU) 2016/426, 2011/65/EU)
- SIL3 — DIN EN 61508
- DIN EN 298
- DIN EN 13611
- DIN EN 50156-1
- DIN EN 50156-2
- IECEx KIWA 20.0005X (Ex zone 2 version with integrated power unit)
- ITS 15 ATEX 18302X, IECEx ITS 15.0041X (external power unit for Ex zone 1)
Accessories
- Sliding flange with O-ring seal in 1.4571 stainless steel: DN50 PN6 for GFI48 (special 2-hole type also available), DN65 PN6 for GFI70, DN80 PN6 for GFI89
- Thermal jacket for GFI pilot burners
- High-pressure needle valve for the GFI pilot burners
- Gas ball valves (GFI48, GFI70, GFI89): DVGW-approved brass (1/2", 3/4", 1 1/2" or 2"). Also a 3/4" mini type and a 3" DN80 stainless steel type with lever
- Stainless steel double nipples and NPT–R hexagon reducing nipples (GFI48, GFI70, GFI89)
- Air regulating sleeve (GFI48, GFI70, GFI89): 3/4", 1", 1 1/2" or 2" female thread, black cast iron
- Stainless steel pressure gauge (GFI48, GFI70, GFI89): 0…160 mbar, Ø 63 mm case, G1/8" vertical connection
- Feed-through flange supplied with seal and bolts
Documents
- Data sheet · GFI Electronics (opens in a new tab)
- Data sheet · GFI Flange (opens in a new tab)
- Data sheet · GFI35 (opens in a new tab)
- Data sheet · GFI48 (opens in a new tab)
- Data sheet · GFI70 (opens in a new tab)
- Data sheet · GFI89 (opens in a new tab)
- Operating manual (opens in a new tab)
- Product catalogue (opens in a new tab)
More products in this group
HEI high-energy igniter
Igniter that lights the main fuel directly by spark, without pilot fuel, with control unit and lance in a single unit
- 18 J (HEI500) · 10 J (HEI600)
- NFPA 8501/8502 Class 3 Special
- Ex zone 2 (optional)
TP series pilot torches
Gas-fired pilot torches from 2 to 600 kW for dependable main burner ignition, available as venturi self-aspirating or forced-air versions
- 2 … 600 kW
- Venturi or forced air
- HV or HE ignition
TP60 / TP76 forced-draft pilot torches with UV flame detection
Forced-draft pilot torches of up to 250 kW and up to 600 kW, with the flame watched by an ionisation rod or an integrated UV detector
- ≤ 250 kW · ≤ 600 kW
- Forced draft
- Ionisation or UV flame detection
XEC10 high-energy ignition unit
Heavy-duty wall-mounted unit delivering 10 J per spark at 24 sparks per second, able to light diesel and heavy fuel oil directly
- 10 J · 24 Hz
- 1400 V
- IP66
Let's choose the right product for your project together