Steam accumulator
Insulated pressure tank that covers sudden steam peaks as stored superheated water flashes into steam
TSB Energy
- EN 13445 · 2014/68/EU
- Ex zone 1 (optional)
- Modbus TCP/IP · Profinet
A steam accumulator is an insulated cylindrical tank holding superheated water and steam under pressure. Steam from the boiler enters through a perforated pipe near the bottom; part of it condenses and heats the water, and the rest fills the space above the water level. Fully charged, it is about three-quarters full of water, with temperature and pressure raised. When steam demand exceeds boiler capacity, the accumulator takes over: as steam is drawn off, pressure falls slightly and some of the hot water flashes into steam. Most of the energy sits in the water at saturation temperature rather than in the steam space, so the more water the tank holds, the better it absorbs load swings.
The accumulator evens out peak loads on the boiler and prevents the surging, water carry-over and impurity entrainment that sudden pressure drops cause, so the plant runs without pressure swings in busy and quiet periods alike. Sizing starts from peak and average steam demand, peak duration and boiler capacity to find the steam deficit; an efficiency factor of 90 % is applied, the volume is derived from operating pressure and temperature, and a 20 % safety margin is added. Typical uses include power plants, textile finishing, canning, aerated concrete and EPS production, rubber autoclaves, sterilisation and heat storage in solar energy systems.
The tank is delivered on a single skid and only needs connecting to power, feedwater and steam users. A demister at the outlet holds back moisture for very dry steam, and a vacuum breaker protects the tank from the negative pressure that forms as it cools while out of service. Shell and end plates are P355GH to EN 10028-2, nozzle tubes P235GH or P265GH, with 100 mm of high-density insulation. The PLC supervises overpressure protection, staged water level safeguards, steam temperature and emergency shutdown, with data via Modbus, Modbus TCP/IP or Profinet. On request, a version certified to ATEX for Ex zone 1 is built.
Steam accumulator
- Responds at once to sudden steam draw, without water carry-over from the boiler
- Balances energy demand for precise operation without pressure swings
- Evens out peak loads on the boiler and improves energy efficiency
- Briefly delivers steam far above the boiler's maximum output
- Demister for very dry steam and vacuum breaker against negative pressure
- Access to the water side through inspection covers
- Optional ATEX version for Ex zone 1
- Remote monitoring via Modbus, Modbus TCP/IP and Profinet
Steam accumulator
Demister
Unit on the steam outlet that holds back the moisture carried by the steam, giving steam of high dryness.
Vacuum breaker
While the accumulator is out of service it loses heat to its surroundings, the inside temperature drops and negative pressure forms; the vacuum breaker is the safety device that protects the tank against it.
Key specifications
| Specification | Steam Accumulator |
|---|---|
| Water fill level | ≈ 50 … 75 % (typical) |
| Thermal insulation | 100 mm, high-density insulation material |
| Material | P355GH (shell) · P235GH / P265GH (nozzle pipes) |
| Explosion protection (Ex) | Ex zone 1 · ATEX (optional) |
| Interfaces | Modbus · Modbus TCP/IP · Profinet |
Approvals and standards
- CE declaration of conformity — 2014/68/EU (pressure equipment)
- EN 13445 — unfired pressure vessels (design and manufacture)
- TRD — German technical rules for steam boilers
- ASME VIII Div. 1 — pressure vessels (design and manufacture)
- ATEX — Ex zone 1 (optional Ex version)
Accessories
- PLC supporting communication protocols such as Modbus and Profibus
More products in this group
Three-pass steam boiler
Scotch-type fire-tube boiler for industry: up to 30 000 kg/h of steam at pressures up to 25 bar
- ≤ 30 000 kg/h
- ≤ 21 000 kW
- ≤ 25 bar
Water-tube steam boiler
Low-water-content boiler that raises steam in 10–15 minutes: up to 80 000 kg/h of steam at up to 160 bar
- ≤ 80 000 kg/h
- ≤ 160 bar
- Efficiency ≥ 95 %
Mobile steam boiler room
Complete steam boiler house in a 20 ft or 40 ft ISO container, factory-tested and ready to connect
- ≤ 6000 kg/h
- ≤ 16 bar
- ISO 20 ft / 40 ft
Liquid and gas-fired thermal oil heater
Forced-circulation coil heater that brings thermal oil up to 420 °C in a closed loop (special equipment above 300 °C)
- ≤ 420 °C (special equipment > 300 °C)
- ≤ 12 000 kW
- ≤ 25 bar
Let's choose the right product for your project together
Tell us about your plant and what you need, and our engineers will recommend the right solution.