HAB indirect-fired air heater
Non-pressurised heater delivering clean air of up to 380 °C that never touches the combustion products
TSB Energy · HAB
- ≤ 7000 kW
- ≤ 380 °C
- Turndown 20:1
- Gas · Oil
In the HAB, clean air flows continuously at 5–6 m/s around the combustion chamber and the flue tubes, in turbulent flow with no dead zones. It takes up the heat of the flame and flue gases through the tube and chamber walls and never mixes with the combustion products. The heater is non-pressurised and can be built horizontally or vertically. TSB supplies the HAB for diesel, fuel oil, natural gas, LPG, LNG or biogas, with a heat output of up to 7000 kW (6 000 000 kcal/h) and clean air temperatures of up to 380 °C.
Burner and driven clean-air fan run together under PID control; modulation sets the heat input over a range of up to 20:1 and keeps the process air outlet temperature fully under control. Heating begins 10–15 seconds after start-up. Compared with steam heating, the HAB avoids condensate, flash steam and blowdown losses, needs no make-up water and discharges no waste water. It can sit upstream or downstream of the process air fan under positive or negative pressure. With clean combustion, NOx stays below 70 mg/Nm³ on gas and below 150 mg/Nm³ on liquid fuel; with a suitable burner it can fire up to 100 % hydrogen.
Three insulation layers on the front door and the rear chamber door — Hycast SS alumina-enriched refractory concrete, ceramic fibre blanket and ceramic paper — keep the doors safe to touch, and the outer wall has 100 mm of high-density insulation. Shell and covers are P355GH boiler plate or, for hygienic applications, AISI304 stainless sheet; flue tubes are AISI304 or AISI321, and tube plates and combustion chamber AISI310S and AISI253 high-temperature stainless steel. The PLC monitors the air flow pressure switch, outlet temperature protection, flue and surface temperatures; data go out via Modbus, Modbus TCP/IP or Profinet. Design follows EN 13445 and ASME Section VIII Div. 1.
HAB indirect-fired air heater
- Clean air never touches combustion products, which suits drying and food processes
- Heating begins 10–15 seconds after start-up, with no standby losses
- Non-pressurised with no intermediate fluid: no water treatment, freezing or leakage
- Heat input modulated over up to 20:1, with micro-modulation as standard on the burner
- Diesel, fuel oil, natural gas, LPG, LNG, biogas; up to 100 % hydrogen with a suitable burner
- Low NOx with clean combustion; optional O₂/CO trim and recuperator for higher efficiency
- According to TSB, 25–35 % fuel savings compared with steam and thermal oil systems
- Remote monitoring via Modbus, Modbus TCP/IP and Profinet
HAB indirect-fired air heater
Burner
Burner fully matched to the HAB for gas or liquid fuel, with micro-modulation as standard. Burner modulation and the clean-air fan drive are controlled together by PID according to process demand; with a suitable burner, up to 100 % hydrogen can be fired.
Clean-air fan
Sized to each application's flow rate and back pressure, it keeps the film temperature on the heating surfaces within safe limits. Redesigned tube diameters and flue gas paths lower boiler and air back pressure, so a smaller fan motor is sufficient.
Key specifications
| Specification | HAB |
|---|---|
| Thermal capacity | ≤ 7000 kW (≤ 6 000 000 kcal/h) |
| Operating temperature | ≤ 380 °C |
| Fuel types | Natural gas, LPG, LNG, biogas, diesel, heavy fuel oil, H₂ (up to 100 % with a suitable burner) |
| Turndown ratio | ≤ 20:1 |
| Time to heat after start-up | 10 … 15 s |
| Flow velocity | 5 … 6 m/s |
| NOx emissions | Clean combustion: < 70 mg/Nm³ (gas firing) · < 150 mg/Nm³ (oil firing) |
| Material | Shell and covers: P355GH / AISI304 · boiler tubes: AISI304 / AISI321 · combustion chamber: AISI310S / AISI253 |
| Interfaces | Modbus · Modbus TCP/IP · Profinet |
Approvals and standards
- EN 13445 — unfired pressure vessels (design and manufacture)
- TRD — German technical rules for steam boilers
- ASME VIII Div. 1 — pressure vessels (design and manufacture)
Accessories
- Recuperator heating the combustion air with flue gas
- O₂ and CO trim control
- Firing options for two fuels or fuel mixtures
- Safety temperature sensors and flow sensors
- Air ducts and flue systems
- PLC supporting communication protocols such as Modbus and Profibus
More products in this group
Three-pass steam boiler
Scotch-type fire-tube boiler for industry: up to 30 000 kg/h of steam at pressures up to 25 bar
- ≤ 30 000 kg/h
- ≤ 21 000 kW
- ≤ 25 bar
Water-tube steam boiler
Low-water-content boiler that raises steam in 10–15 minutes: up to 80 000 kg/h of steam at up to 160 bar
- ≤ 80 000 kg/h
- ≤ 160 bar
- Efficiency ≥ 95 %
Mobile steam boiler room
Complete steam boiler house in a 20 ft or 40 ft ISO container, factory-tested and ready to connect
- ≤ 6000 kg/h
- ≤ 16 bar
- ISO 20 ft / 40 ft
Liquid and gas-fired thermal oil heater
Forced-circulation coil heater that brings thermal oil up to 420 °C in a closed loop (special equipment above 300 °C)
- ≤ 420 °C (special equipment > 300 °C)
- ≤ 12 000 kW
- ≤ 25 bar
Let's choose the right product for your project together
Tell us about your plant and what you need, and our engineers will recommend the right solution.




