NT1 NOx measuring system

Direct O₂ and NOx measurement in flue gas with KS2DNOx probes; up to 4 probes depending on version, touch panel

Flue gas measurement

LAMTEC · NT1

  • O₂ + NOx
  • 1 / 2 / 4 × KS2DNOx
  • Touch panel

NT1 is LAMTEC's microprocessor-based NOx transmitter for the KS2DNOx combination probe. It simultaneously measures O₂ concentration and nitrogen oxides in flue gas from combustion plants operating with excess air (λ > 1); the NOx reading is the sum of NO and NO₂. Measurement takes place in situ in the moist flue gas, with no sample gas conditioning. The readings are used for monitoring and optimisation.

NT1 is operated from a 5.7-inch resistive touch panel on the front door, which handles password entry, NOx and O₂ values and trends, probe, fuel, warning and fault information, calibration, analogue and digital output settings, LSB activation and USB logging settings. There are three versions: one for a single probe with LSB, and two without LSB for up to two or up to four probes. The LSB version can work together with other LAMTEC systems. Up to 8 analogue and up to 12 digital outputs can be connected, and the USB port on the panel is for continuous logging of measurement data.

With the GED BASE gas extraction device, the KS2DNOx probe measures at up to 550 °C and up to 100 mg/Nm³ of dust; with GED FLEX, at up to 1400 °C depending on material and, with purging, up to 1000 mg/Nm³ of dust. O₂ accuracy is ±8 % of reading (not better than ±0.2 vol.%) and NOx accuracy ±10 % of reading (not better than ±3 ppm); the t60 response time is under 10 s for both O₂ and NOx. NT1 runs on 120…230 V AC, has IP65 protection and operates at 0…+50 °C; it is ready to measure about 10 minutes after mains on, or 60 minutes after first commissioning of the probe.

NT1 NOx measuring system
NT1 NOx measuring system 1NT1 NOx measuring system 2NT1 NOx measuring system 3NT1 NOx measuring system 4NT1 NOx measuring system 5
Benefits

NT1 NOx measuring system

  • Simultaneous O₂ and NOx measurement with the KS2DNOx probe
  • In-situ measurement directly in the flue gas; no sample gas conditioning needed
  • Short response time: t60 < 10 s for O₂ and NOx
  • Depending on version, 1 probe, up to 2 or up to 4 probes per NT1
  • 5.7-inch touch panel for readings and operation; continuous data logging via USB
  • Readings for monitoring and optimisation; LSB connection to LAMTEC systems in the single-probe version
Modules

NT1 NOx measuring system

KS2DNOx combination probe

Combination probe that measures O₂, NO and NO₂ in situ and combines the nitrogen oxides into a NOx value. It comes with a calibrating gas connection and an IP65 junction box, and the probe housing is stainless steel (1.4571/1.4404). It is used with the GED BASE or GED FLEX gas extraction device; the permissible flue gas temperature at the probe head is below 450 °C. It reaches the specified accuracy after about 7 minutes.

NT1

Key specifications

General data
SpecificationNT1
Measuring rangeO₂: 0 … 21 % · NOx: 0 … 1000 ppm / 0 … 2000 mg/Nm³
Measuring accuracy (O₂)±8 % (of reading, not better than ±0.2 vol.%)
Measuring accuracy (NOx)±10 % (of reading, not better than ±3 ppm / ±6 mg/Nm³)
Number of connectable probes1 · ≤ 2 · ≤ 4 (version-dependent)
InterfacesLSB (single-probe version) · USB
Supply voltage120 V AC -25 % … 230 V AC +15 %, 50–60 Hz
Degree of protectionIP65
Ambient temperature0 … +50 °C
Probe data
SpecificationKS2DNOx + GED BASEKS2DNOx + GED FLEX
Max. flue gas temperature≤ 550 °C≤ 1400 °C (material-dependent)
Dust concentration≤ 100 mg/Nm³≤ 1000 mg/Nm³ (with purging)

Full technical data: data sheet(opens in a new tab)

Approvals and standards

  • CE declaration of conformity (2014/35/EU, 2014/30/EU, 2011/65/EU)
  • DIN EN 61326-1
  • DIN EN 61010-1

Accessories

  • Analogue output module: 4 current (0/4…20 mA) or voltage (0…10 V) outputs per module; with up to 2 modules, O₂ and NOx values for each probe
  • Digital output module: 6 configurable outputs per module; with up to 2 modules, NOx high, O₂ low and sensor fault messages for each probe

Documents