Deluxia Palace, Barbaros Mah. Mor Sümbül Sok. No:5A/88 Kat:3, Ataşehir / İstanbul [email protected]

LT3 measuring system

Compact, robust measurement of O₂ and CO/H₂ in flue gas

Flue gas measurement

LAMTEC · LT3

  • O₂ + COe
  • SIL1 / SIL2

LT3 is a compact measuring system that combines the LAMTEC lambda transmitter with an LS2 or KS1D probe. With the LS2 probe it measures oxygen in the flue gas; with the KS1D probe it measures oxygen and, at the same time, the sum of unburnt components (COe).

The measured values form the basis for setting the fuel-air ratio and for combustion optimisation. LT3 is an economical alternative to the more flexible LT2: the standard version is SIL1 certified, and the two-transmitter configuration is SIL2 certified.

LT3 measuring system
LT3 measuring system 1LT3 measuring system 2LT3 measuring system 3
Benefits

LT3 measuring system

  • Oxygen measurement with the LS2 probe; oxygen and COe measurement with the KS1D probe
  • Robust, compact steel housing; stainless steel as an option
  • Cost-effective, field-proven and low-maintenance design
  • SIL1 in the standard version (DIN EN 61508)
  • SIL2 configuration with two transmitters (DIN EN 50156-1, DIN EN 61511-1)
Modules

LT3 measuring system

LS2 probe

Lambda probe that directly measures the oxygen concentration in the flue gas.

KS1D combination probe

Combination probe that measures oxygen together with the sum of unburnt components (COe) such as CO and H₂.

LT3

Key specifications

SpecificationLT3
Measuring rangeO₂: 0 … 21 % · COe (KS1D): 0 … 1000 ppm (0 … 10 000 ppm on request)
Measuring accuracy (O₂)±5 % (of reading, not better than ±0.3 vol.%)
Response time (t90)O₂: < 9 s · COe: < 13 s
Max. flue gas temperature≤ 1400 °C (probe-dependent)
Degree of protectionIP65 · IP42 (probe-dependent)
FuelsLight fuel oil, natural gas
Safety integrity levelSIL1 · SIL2 (1oo2)

Full technical data: data sheet(opens in a new tab)

Approvals and standards

  • CE declaration of conformity (2014/35/EU, 2014/30/EU, 2011/65/EU)
  • EU type examination certificate — DIN EN 16340 (with KS1D)
  • DIN EN 60730-1
  • UL 60730-1 (US)
  • CSA E60730-1 (CA)
  • SIL1 — DIN EN 61508
  • SIL2 — DIN EN 50156-1, DIN EN 61511-1

Accessories

  • Analogue current and voltage output module (0/4…20 mA, 0/2…10 V)
  • Digital output module for operating, status and limit value messages
  • PROFIBUS DP module
  • Efficiency calculation module with flue gas temperature measurement

Documents