Deluxia Palace, Barbaros Mah. Mor Sümbül Sok. No:5A/88 Kat:3, Ataşehir / İstanbul [email protected]

662RX 30, 40 and 50 Nm actuator

30, 40 and 50 Nm actuators with three-point step or optional 4…20 mA control, TÜV-approved for ETAMATIC, FMS and VMS

Burner Control Systems

LAMTEC · 662R2112 · 662R2121 · 662R2122

  • 30 / 40 / 50 Nm
  • IP65
  • ETAMATIC · FMS · VMS
  • 4 … 20 mA (optional)

Types 662R2112 (30 Nm), 662R2121 (40 Nm) and 662R2122 (50 Nm) are electric LAMTEC actuators that move dampers and valves in firing plants. They are TÜV-approved for operation with ETAMATIC, FMS and VMS and also suit other combustion and industrial applications. The standard version runs on 230 V AC / 50 Hz, uses three-point step control and turns through 90° in 60 seconds. When ordering, 115 V AC or 230 V AC supply at 50 or 60 Hz, running times of 30 or 40 seconds and angular displacements of 120°, 135°, 180° or 270° can be selected.

In the three-point step version, position is reported by a TÜV-approved 5 kΩ conductive-plastic potentiometer from NOVOTEC or CONTELEC, coupled positively and without backlash; a wire-wound 100 Ω, 200 Ω or 1 kΩ potentiometer can be chosen instead. This version is supplied only with an electric manual override operated by an OPEN/CLOSE push button. With a 60-second running time, the actuators satisfy the safety requirements for tested potentiometers coupled in this way; the running time can change with the limit switches and potentiometers fitted.

Optional integrated electronic control drives the actuator with a 4…20 mA signal; this version reports its position as 4…20 mA and is supplied without manual override. With ETAMATIC, FMS or VMS, this feedback does not count as a fail-safe position indication, so an additional TÜV-approved 5 kΩ conductive-plastic potentiometer is mandatory. The aluminium housing with metal cover provides IP65 protection; the ambient temperature range is -10…+60 °C, extending down to -30 °C with the optional 15 W housing heater with thermostat. A coupling or lever has to be ordered separately.

662RX 30, 40 and 50 Nm actuator
662RX 30, 40 and 50 Nm actuator 1662RX 30, 40 and 50 Nm actuator 2
Benefits

662RX 30, 40 and 50 Nm actuator

  • Torque of 30 Nm (662R2112), 40 Nm (662R2121) or 50 Nm (662R2122)
  • TÜV-approved for operation with ETAMATIC, FMS and VMS
  • TÜV-approved NOVOTEC or CONTELEC 5 kΩ conductive-plastic feedback potentiometer
  • Optional integrated electronic control for operation with a 4…20 mA signal
  • Two limit switches and two additional switches as standard; zero to four additional switches can be selected, gas-tight versions are available
  • Ø12 × 30 mm shaft with 4 × 4 × 20 mm feather key
  • Aluminium housing with metal cover (IP65) and two M20 × 1.5 cable glands for Ø 8–13 mm cables
  • -10…+60 °C ambient temperature, down to -30 °C with the optional housing heater
662R2112 · 662R2121 · 662R2122

Key specifications

Specification662R2112662R2121662R2122
Torque30 Nm40 Nm50 Nm
Running time (90°)60 s (standard version) · 30 / 40 s (optional)60 s (standard version) · 30 / 40 s (optional)60 s (standard version) · 30 / 40 s (optional)
Supply voltage115 / 230 V AC · 50 / 60 Hz (230 V AC / 50 Hz standard version)115 / 230 V AC · 50 / 60 Hz (230 V AC / 50 Hz standard version)115 / 230 V AC · 50 / 60 Hz (230 V AC / 50 Hz standard version)
Control3-point step · 4 … 20 mA (optional)3-point step · 4 … 20 mA (optional)3-point step · 4 … 20 mA (optional)
Position feedback5 kΩ potentiometer (conductive plastic) · 4 … 20 mA (with electronic control)5 kΩ potentiometer (conductive plastic) · 4 … 20 mA (with electronic control)5 kΩ potentiometer (conductive plastic) · 4 … 20 mA (with electronic control)
Manual overrideElectric (3-point step version only)Electric (3-point step version only)Electric (3-point step version only)
Degree of protectionIP65IP65IP65
Ambient temperature-10 … +60 °C-10 … +60 °C-10 … +60 °C
Weight2.5 kg2.5 kg2.5 kg
Output shaftØ12 × 30 mm, feather key 4 × 4 × 20 mmØ12 × 30 mm, feather key 4 × 4 × 20 mmØ12 × 30 mm, feather key 4 × 4 × 20 mm

Approvals and standards

  • CE declaration of conformity (2014/35/EU, 2014/30/EU, 2011/65/EU)
  • DIN EN 60730
  • TÜV approval (for use with ETAMATIC, FMS and VMS)

Documents

Let's choose the right product for your project together

Tell us about your plant and what you need, and our engineers will recommend the right solution.