Deluxia Palace, Barbaros Mah. Mor Sümbül Sok. No:5A/88 Kat:3, Ataşehir / İstanbul [email protected]

XEC03H high-energy ignition module

Panel-mounted high-energy module for flare ignition, giving 18 J per spark even with a power supply cable of up to 500 m

Flare Systems

TESI · XEC03H

  • 18 J · 2 Hz
  • 1000 V DC
  • ≤ 500 m power supply cable
  • IP65

XEC03H is TESI's high-energy ignition module for installation in electrical panels, used to light ground and elevated flares. In a flare layout the ignition power supply often has to sit far from the ignition rod, and a long cable weakens the spark; XEC03H is designed to keep the spark strong with a power supply cable of up to 500 m.

It is fed with 115–230 V AC, 50/60 Hz (12/24 V DC on request), draws 110 W and produces 18 J (±10 %) per spark at 2 sparks per second from a 1000 V DC output. The duty cycle is 33 %, with sparking lasting up to 1 minute. The powder-coated steel housing is rated IP65, measures 170 × 140 × 85 mm and weighs 5 kg; input and output connections are made with two 1 m cables. Thermocouple or ionisation flame detection is available as an option.

Its new housing is resin-filled, keeping water out in any weather outdoors. The compact module fits easily on a mounting plate, the wiring is simple and it can be exchanged quickly even with the plant running. XEC03H serves flare ignition where process gas is burnt off: in refineries, chemical and petrochemical plants and on offshore platforms.

XEC03H high-energy ignition module
XEC03H high-energy ignition module 1XEC03H high-energy ignition module 2XEC03H high-energy ignition module 3XEC03H high-energy ignition module 4
Benefits

XEC03H high-energy ignition module

  • Strong spark even with a power supply cable of up to 500 m
  • 18 J per spark, 2 sparks per second, 1000 V DC output
  • Resin-filled, fully waterproof housing; IP65
  • Compact size for a mounting plate: 170 × 140 × 85 mm, 5 kg
  • Simple wiring; can be exchanged quickly even with the plant running
  • Thermocouple or ionisation flame detection option
  • 12/24 V DC supply on request
XEC03H

Key specifications

SpecificationXEC03H
Ignition energy18 J ± 10 %
Spark rate2 Hz (average)
Output voltage1000 V DC
Supply voltage115–230 V AC, 50/60 Hz (12/24 V DC on request)
Power consumption110 W
Duty cycle33 % (≤ 1 min sparking)
Cable length≤ 500 m (power supply cable)
Flame detectionThermocouple (optional) · Ionisation (optional)
Degree of protectionIP65
Dimensions170 × 140 × 85 mm

Full technical data: data sheet(opens in a new tab)

Accessories

  • Optional safety back-up: an additional ignition module on a UPS, or a portable igniter whose battery is recharged by solar panels

Documents

Let's choose the right product for your project together

Tell us about your plant and what you need, and our engineers will recommend the right solution.